XLPE Insulation Control cable
It is used in controlling ,supervising loop and protecting circuit cases of A.C. rated voltage 450/750V or lower .
Executive standard : GB/T 9330-2008
Working Condition
1: Long-term working temperature allowed by cable conductor is 90℃.
2: Environment temperature for installation should be no less than 0℃, allowed bending radius is stipulated as follows : It should be no less than 8 times that of cable OD for unarmored cable ;It should be no less than 12 times that of cable OD for armored .
Codes Meaning
Series code...............................................................................K
Material Code
Copper conductor.....................................................................omitted
XLPE or crosslinked polyolefine insulation................................YJ
PVC sheath ..............................................................................V
PE or Polyolefine sheath...........................................................Y
Classified by Structure and Performance
Braided shielding ......................................................................P
Copper tape shielding ..............................................................P2
Soft structure............................................................................R
Aluminum-polyester tape shieding ...........................................P3
Dual steel tape armor...............................................................2
Steel wire armored...................................................................3
Type and Description
Table 1
|
Type
|
Description
|
|
KYJV
|
Control cable with Cu core, XLPE insulation, PVC sheath
|
|
KYJVP
|
Control cable with Cu core, XLPE insulation,PVC sheath, copper wire braided shielding
|
|
KYJVP2
|
Control cable with Cu core,XLPE insulation,PVC sheath ,copper tape shielding
|
|
KYJVP3
|
Control cable with copper conductor,XLPE insulation,PVC sheath,aluminum-polyester tape shielding
|
|
KYJV22
|
Control cable with Cu core, XLPE insulation,PVC sheath ,steel tape armor
|
|
KYJVP2-22
|
Control cable with Cu core,XLPE insulation,PVC sheath,copper tape shielding ,steel tape armor
|
|
KYJV32
|
Control cable with Cu conductor ,XLPE insulation,PVC sheath and steel wire armored
|
Prefix ZA-、ZB-、ZC- is added to the original type for indication of flame resistance cable ,for example,ZA-KYJV.
We also produce unlisted type of cables as required ,such as KYJVP2-23,KYJY33 and so on .
Technical Parameter
DC resistance of finished cable conductor at 20℃ in table 2
|
ltem
|
unit
|
Technical indices
|
|
DC resistance of conductor at
20℃
|
Ω/km
|
cross section area mm2
|
0.75
|
1.0
|
1.5
|
2.5
|
4
|
6
|
10
|
|
Category A,B
|
24.5
|
18.1
|
12.1
|
7.41
|
4.61
|
3.08
|
1.83
|
|
Category R
|
26.0
|
19.5
|
13.3
|
7.98
|
/
|
/
|
/
|
2: Finished cable should bear A.C.voltage of 3.0 KV under power frequency for 5min without puncture of insulation.
DC resistance of finished cable conductor at 90℃in table 3
|
ltem
|
unit
|
Technical indices
|
|
DC resistance of conductor at
90℃
|
Ω/km
|
cross section area mm2
|
0.75
|
1.0
|
1.5
|
2.5
|
4
|
6
|
10
|
|
Category A
|
1.20
|
1.10
|
1.10
|
1.0
|
0.85
|
0.70
|
/
|
|
Category B
|
1.4
|
1.30
|
1.0
|
0.90
|
0.77
|
0.65
|
0.65
|
4: Control cable with XLPE insulation has good features of heat resistance, freezing resistance, chemistry resistance ,insulated resistance and long lifetime compared with control cable with PVC insulation.